CFD analyses on the thermal comfort conditions of a cooled room: A case study

dc.authorid0000-0002-3065-1942
dc.contributor.authorÖzsağıroğlu, Semih
dc.contributor.authorCamcı, Muhammet
dc.contributor.authorTaner, Tolga
dc.contributor.authorAçıkgöz, Özgen
dc.contributor.authorDalkılıç, Ahmet Selim
dc.contributor.authorWongwises, Somchai
dc.date.accessioned2021-05-17T10:25:12Z
dc.date.available2021-05-17T10:25:12Z
dc.date.issued2022
dc.departmentTeknik Bilimler Meslek Yüksekokulu
dc.descriptionTaner, Tolga ( Aksaray, Yazar )
dc.description.abstractThis study examined a room with a surface of 1.8 x 1.8 x 2.85 (m) and a well-insulated floor (adiabatic condition) and examined the heat exchange from the side surfaces and ceiling. In this closed room, the heat transfer effects with radiation were investigated while bringing them to comfort conditions ranging from 30 (degrees C) air temperature to 20-24 (degrees C). A computer with a power of 25 (W) as a source of heat, a person with an average metabolic activity of 50-70 (W) and a table were found in this closed room. In this study, the cooling of the room from the floor, ceiling and air conditioner was inquired while the computer was running, in a closed area under the specified heat transfer conditions. As a scenario, the air exchange coefficient was modeled via Ansys Fluent, fed with air of 15 (degrees C) with 1, 3, 5, 10, 15 air. In addition, the comfort values of the human wrist (the distance of 0.1 m) and the shoulder (the distance of 1.1 m) were researched according to ASHRAE-55. The obtained results were analyzed as a comparison of ACH results, and the comfort parameter values were analyzed by reading the sections taken from the ankle shoulder level and velocity, temperature, values according to ANSI/ASHRAE-55. The relative humidity was 50% in the room, while the metabolic activity is 1.2 (met). These parameters corresponded to the sitting position; the clothing effect was found to be 0.67 (clo). The novelty of this study encourages the production of the ideal CFD analysis on the thermal comfort conditions of a cooled room, the task of engineering.
dc.identifier.doi10.1007/s10973-021-10612-w
dc.identifier.endpage-en_US
dc.identifier.issue-en_US
dc.identifier.scopusqualityQ1
dc.identifier.startpage-en_US
dc.identifier.urihttps:/dx.doi.org/10.1007/s10973-021-10612-w
dc.identifier.urihttps://hdl.handle.net/20.500.12451/7955
dc.identifier.volume-en_US
dc.identifier.wosWOS:000621761900030
dc.identifier.wosqualityQ1
dc.indekslendigikaynakWeb of Science
dc.indekslendigikaynakScopus
dc.language.isoen
dc.publisherSpringer
dc.relation.ispartofJournal of Thermal Analysis and Calorimetry
dc.relation.publicationcategoryMakale - Uluslararası Hakemli Dergi - Kurum Öğretim Elemanı
dc.rightsinfo:eu-repo/semantics/embargoedAccess
dc.subjectComfort
dc.subjectComputational Fluid Dynamics
dc.subjectFloor Cooling
dc.subjectCeiling Cooling
dc.subjectAir Conditioner System
dc.subjectAnsys Fluent
dc.titleCFD analyses on the thermal comfort conditions of a cooled room: A case study
dc.typeArticle

Dosyalar

Orijinal paket
Listeleniyor 1 - 1 / 1
Yükleniyor...
Küçük Resim
İsim:
ozsagiroglu-semih -2021.pdf
Boyut:
4.89 MB
Biçim:
Adobe Portable Document Format
Açıklama:
Tam Metin / Full Text
Lisans paketi
Listeleniyor 1 - 1 / 1
[ X ]
İsim:
license.txt
Boyut:
1.44 KB
Biçim:
Item-specific license agreed upon to submission
Açıklama: