Comparing the energetic and exergetic performances of a building heated by solar energy and ground-source (geothermal) heat pump

dc.contributor.authorHepbaşli, Arif
dc.contributor.authorBalta, Mustafa Tolga
dc.contributor.authorAlsuhaibani, Zeyad
dc.contributor.editorPan, W
dc.contributor.editorRen, JX
dc.contributor.editorLi, YG
dc.date.accessioned13.07.201910:50:10
dc.date.accessioned2019-07-16T09:20:08Z
dc.date.available13.07.201910:50:10
dc.date.available2019-07-16T09:20:08Z
dc.date.issued2012
dc.departmentMühendislik Fakültesi
dc.descriptionInternational Conference on Energy, Environment and Sustainable Development (ICEESD 2011) -- OCT 21-23, 2011 -- Shanghai Univ Elect Power, Shanghai, PEOPLES R CHINA
dc.descriptionWOS:000309147801004
dc.description.abstractIn this study, we considered a building, which had a volume of 336 m(3) and a floor area of 120 m(2), with indoor and outdoor air temperatures of 20 degrees C and 0 degrees C, respectively. For heating this building, we selected two options, namely (i) a ground-source (geothermal) heat pump system (Case 1), and (ii) a solar collector heating system (Case 2). We employed both energy and exergy analysis methods to assess their performances and compare them through energy and exergy efficiencies and sustainability index. We also investigated energy and exergy flows for this building and illustrated from the primary energy transformation through the heat production system and a distribution system to a heating system, and from there, via the indoor air, across the building envelope to the surrounding air. We calculated that the total exergy efficiencies for Cases 1 and 2 were 4.7%, and 26.1% while sustainability index values for both cases were 1.049 and 1.353 at a reference (dead) state temperature of 0 degrees C, respectively.
dc.description.sponsorshipXinjiang Univ, Hebei United Univ
dc.identifier.doi10.4028/www.scientific.net/AMR.347-353.1801
dc.identifier.endpage+en_US
dc.identifier.isbn978-3-03785-265-1
dc.identifier.issn1022-6680
dc.identifier.scopusqualityN/A
dc.identifier.startpage1801en_US
dc.identifier.urihttps://doi.org/10.4028/www.scientific.net/AMR.347-353.1801
dc.identifier.urihttps://hdl.handle.net/20.500.12451/5063
dc.identifier.volume347-353en_US
dc.identifier.wosWOS:000309147801004
dc.identifier.wosqualityN/A
dc.indekslendigikaynakWeb of Science
dc.indekslendigikaynakScopus
dc.language.isoen
dc.publisherTrans Tech Publications
dc.relation.ispartofRenewable and Sustainable Energy
dc.relation.ispartofseriesAdvanced Materials Research
dc.relation.publicationcategoryKonferans Öğesi - Uluslararası - Kurum Öğretim Elemanı
dc.rightsinfo:eu-repo/semantics/closedAccess
dc.subjectRenewable Energy
dc.subjectSolar Energy
dc.subjectGeothermal Energy
dc.subjectGround-source Heat Pump
dc.subjectHVAC
dc.subjectExergy
dc.subjectSustainability
dc.titleComparing the energetic and exergetic performances of a building heated by solar energy and ground-source (geothermal) heat pump
dc.typeConference Object

Dosyalar